POL SERIES LIFT UPS

Range: 6 kVA to 60 kVA (3:3)

POM POWER POL Series lift UPS systems provide emergency power during
outages, ensuring elevators reach the nearest floor and open doors
smoothly. POL Series is a three-phase UPS ranging from 6 kVA to 60 kVA,
with near-zero transfer times, unlike standard generators. When choosing a
system, consider whether it is for minimal emergency rescue or extended
backup. The POL Series UPS manages the elevator’s inrush current, which is
typically three-phase. Advanced options include lithium batteries for longer
life and a more compact design. Compatibility with the elevator’s Variable
Frequency Drive (VFD) is another advantage of POM POWER POL Series UPS,
especially with regenerative VFDs.

FEATURES
  • Suitable for 3 HP to 32 HP
  • 6 kVA - 60 kVA wide capacity options
  • Provides near-zero switching time for smooth
    operation.
  • Able to handle regenerative loads.
  • Capable of offering extended backup durations
  • Phase Fail prevention feature
  • input overload cut-off for additional protection and
    manages high inrush currents
  • Delivers a pure sine wave output.
Technical Specification

TECHNICAL SPECIFICATIONS

Three Phase Input – Three Phase Output

Model POL 306 POL 310 POL 315 POL 320 POL 325 POL 330 POL 340 POL 360
KVA 6 10 15 20 25 30 40 60
Capacity (Balanced Load) 4.8 kW 8 kW 12 kW 16 kW 20 kW 24 kW 32 kW 48 kW
AC INPUT
Input Voltage 415 VAC +15% / -20%
Input Frequency 50 Hz ±6%
Battery Voltage 192 V 240V – 360V 360 V
AC OUTPUT
Technology IGBT Based PWM Inverter using Micro Controller
Output Voltage 380 / 400 / 415 VAC ±2%
Output Frequency 50 Hz ±0.5%
Output Power Factor 0.8
Output Waveform PWM Sine Wave
Crest Factor 3 : 1
Galvanic Isolation Inbuilt Galvanic Isolation Transformer Provided
Harmonic Distortion Less than 3% on Linear Load
Transient Recovery ±4%
Inverter Efficiency Up to 93%
INDICATIONS & ALARMS
Audible Alarm Every 30 sec on mains fail. Battery low pre-alarm at 80% of battery discharge.
Beep for all other trip conditions.
METERING
Digital Metering & Fault Indications Input Voltage, Frequency, Output Voltage, Frequency, Load kW, Battery Voltage, Battery Charge.
Fault Indications – Mains Off, Battery Low Pre-Alarm & Trip, Output Overload.
PROTECTIONS
Protection Features Output Overload (110% – 60 Minutes, 150% – 30 Seconds), Output Short Circuit, Battery Low Trip,
DC Over Voltage, Input Under Voltage / Over Voltage, Input Single Phasing / Phase Reversal, Over Temperature
GENERAL
Bypass Facility Manual
Audible Noise Less than 60 dB at 1 meter
Design Ambient 0 – 60°C
Relative Humidity 0 – 95% (Non-Condensing)
Enclosure M.S. Powder Coated Cabinet with Castor Wheels