DHF SS SERIES UPS

Range: 1 kVA to 20 kVA (1:1/3:1)

The DHF Series 1 kVA to 20 kVA UPS system is a single-phase UPS that uses
advanced technology for a dependable power supply. The DHF Series utilises high
frequency online double conversion technology, providing stable output and
protection against fluctuations. Controlled by Digital Signal Processing (DSP) for accuracy
and efficiency, it includes active power factor correction (APFC), achieving an input power
factor of up to 0.99. This reduces reactive power and enhances energy efficiency. The
system offers output power factor options of 0.9 or 1.0 to meet different load needs.
With a broad input voltage range and a frequency range of 40 to 70 Hz, along with autosensing
and 50/60 Hz conversion, it adapts to various power environments. The “cold start”
function allows activation without external power, which is essential in emergencies.
Battery configurations are flexible, supporting 16 to 20 batteries with digitally controlled
charging for optimal health.

FEATURES
  • Advanced DSP And 3-Level Technology
  • Output Power Factor 1.0
  • Active Power Factor Correction (APFC),
    Input Power Factor Up To 0.99
  • High Efficiency 95% (Up To 98% In ECO
    Mode)
  • Advanced Digital Parallel Technology
  • Flexible Battery Configuration (Settable 16 - 20 PCS Batteries)
  • Digitally Controlled Charge
Technical Specification

TECHNICAL SPECIFICATIONS – DHF SERIES

Single Phase Input – Single Phase Output

MODEL DHF 101 DHF 102 DHF 103 DHF 106 DHF 110
CAPACITY 1kVA / 1kW 2kVA / 2kW 3kVA / 3kW 6kVA / 6kW 10kVA / 10kW
INPUT
Rated Voltage 208 / 220 / 230 / 240 Vac
Voltage Range 110–176 Vac (50–100% derating), 176–280 Vac (No derating), 280–300 Vac (50% derating)
Frequency 40–70 Hz (Auto-sensing)
Power Factor ≥ 0.99
Bypass Voltage Range -25% ~ +15% (Settable)
THDi ≤ 6%
OUTPUT
Voltage 208 / 220 / 230 / 240 Vac (Settable via LCD)
Voltage Regulation ±1%
Frequency 45–65 Hz (Sync Range); 50 / 60 Hz ±0.1 Hz (Battery Mode)
Waveform Sinusoidal
Output Power Factor 0.8 / 0.9 / 1.0 (Factory Settable)
THDv ≤2% (Linear Load); ≤5% (Non-linear Load)
Crest Factor 3:1
Overload 105–125% (1 min); 125–150% (30 sec); >150% (300 ms)
BATTERIES
DC Voltage 24V / 36V 48V / 72V 72V / 96V 192VDC (192–240V Settable)
Max Charging Current 6A 12A
Recharge Time 6–8 hrs (Depends on battery capacity)
SYSTEM
Efficiency ≥90% (Normal Mode); Up to 99% (ECO Mode)
Transfer Time 0 ms (Mains → Battery); 4 ms (Inverter → Bypass)
Protections Short Circuit, Overload, Over Temperature, Battery Discharge, Fan Failure
Communication RS232 (Std), USB / RS485 / Dry Contacts / SNMP (Optional)
Display LCD + LED
Standards IEC 61000-2-2, IEC 62040-1, IEC 62040-2, IEC 62040-3
ENVIRONMENT & OTHERS
Operating Temperature 0°C – 50°C
Storage Temperature -25°C – 70°C
Relative Humidity 0 – 95% (Non-condensing)
Altitude ≥1000m (1% derating per 100m)
IP Rating IP20 / IP21
Noise Level @1m ≤50 dB ≤50 dB ≤50 dB ≤55 dB ≤58 dB
Dimensions (W×D×H) mm 144×417×216 191×495×350
Net Weight (kg) 4 6 8 14.5 16.5
Gross Weight (kg) 5.5 7.5 9.5 16 18

TECHNICAL SPECIFICATIONS

Three Phase Input – Single Phase Output

MODEL DHF310 DHF315 DHF320
CAPACITY 10kVA / 10kW 15kVA / 15kW 20kVA / 20kW
INPUT
Rated Voltage 380 / 400 / 415 Vac
Voltage Range 190 – 305 Vac (50–100% derating); 305 – 499 Vac (No derating)
Rated Frequency 50 / 60 Hz (Auto-sensing)
Power Factor ≥ 0.99
Bypass Voltage Range -40% ~ +15% (Settable)
THDi ≤ 5%
OUTPUT
Rated Voltage 208 (P.F.=0.9) / 220 / 230 / 240 Vac
Voltage Regulation ± 1%
Frequency Synchronized to Bypass (Mains Mode); 50 / 60 Hz ± 0.1 Hz (Battery Mode)
Waveform Sinusoidal
Output Power Factor 0.8 / 0.9 / 1.0 (Factory Settable)
THDv ≤ 1% (Linear Load); ≤ 3% (Non-linear Load)
Crest Factor 3:1
Overload 105%–110% (10 min); 110%–125% (1 min); 126%–150% (30 sec)
BATTERIES
DC Voltage 192 VDC (192 – 240 VDC Settable)
Charging Current 1 – 5 A (Settable), 10 A (Optional)
Recharge Time 8 – 10 Hours (Depends on Battery Capacity)
SYSTEM
Efficiency ≥ 94% @100% load; Max 95% @60% load; ≥ 98% (ECO Mode)
Transfer Time 0 ms
Protections Short Circuit, Overload, Over Temperature, Battery Low Voltage, Over Voltage, Under Voltage, Fan Failure
Max Parallel Connections 4
Communication RS232 (Standard), USB / RS485 / Dry Contacts / SNMP / Battery Temperature Compensation (Optional)
Display LCD + LED
OTHERS
Operating Temperature 0°C – 50°C
Storage Temperature -25°C – 70°C (Without Battery)
Relative Humidity 0 – 95% (Non-condensing)
Altitude ≥1000 m (1% derating per additional 100 m)
IP Rating IP20 / IP21
Noise Level @1m ≤ 58 dB
Dimensions (W×D×H) mm 191 × 495 × 350 191 × 495 × 515
Net Weight (kg) 18.5 26.5
Gross Weight (kg) 20 28