PPXs SERIES

Range: 10 kVA to 500 kVA

The PPXs series UPS is an Online Double Conversion UPS in accordance with IEC EN 62040-3 with a transformer isolated Inverter. Ensuring high quality output, with a compact footprint, PPXs Series designed to protect all kind of loads. PPXs is available from 10 to 500 kVA capacity PPXs Series UPS meets all high reliability requirements of Uninterruptible Power Supply and integrates reliable, safety, maintainability characteristics of a new generation low frequency UPS.

FEATURES

  • Online double-conversion with full DSP control
  • 100% unbalance load capability
  • Output Power Factor 0.9
  • Generator compatible
  • Support battery cold start and auto-restart when mains power is restored
  • ECO mode operation for energy saving Superior protection
  • 7 inches LCD touch screen, user friendly man & machine interface
  • Front access makes maintenance and replacement simplified (160 to 500 kVA)
  • Intelligent self-diagnosing function, all kinds of failure protection, large capabilityof history records storage
  • High MTBF (> 200,000 h) Low MTTR (< 0.5 h)
  • Standard emergency power off(EPO)
  • Standard RS 232, RS 485, Dry contacts Communication Port
Detailed Specification

Description

FULL DIGITALIZED TECHNOLOGY

The PPXs Series UPS have Dual-DSP control chip, advanced control technology, enhanced logic management and eliminated zero drift with analog control, convenient use of modern control technology, convenient debugging, system update and maintenance, perfect logic functions, diverse interactive data for the customers, convenient communication and network functions. The UPS is coming with Optional Advanced user friendly Digital front panel touch screen Display.

FLEXIBILITY

The PPXs Series UPS is suitable for a wide range of applications including IT and the most demanding industrial environments suitable for power capacitive loads such as blade servers, without any reduction of the active power, from 0.8 lagging to 0.9 leading. With a broad of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the UPS Group Synchroniser (USG) and Parallel Systems Joiner (PSJ) sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability.

SMART BATTERY MANAGEMENT

Traditionally when a mains supply is present, the UPS charges it’s Batteries. The inverter uses the power from batteries during input fail. Efficient and intelligent battery management and care is essential to the overall performance of the UPS in an emergency. PPXs Series Smart Battery Management have a range of features designed to provide optimum performance and enhanced operating life.

  • Dual level Charging regime to optimize recharge currents and reduced recharge times
  • Temperature compensation and deep discharge protection to reduce overall battery aging
  • Compatible with different Battery Technologies including Lithium Ion (Optional)
  • Advanced battery self-testing to spot potential battery deterioration and failure.
  • Chargeblock system to reduce electrolyte consumption and lengthen the life of VRLA Batteries

MINIMUM IMPACT ON UTILITY SUPPLIES

The PPXs Series UPS technology removes the problems of oversizing downstream power sources. The UPS features advanced input current absorption techniques including progressive rectifier start-up and the option to reduce battery charging currents. These features make PPXs one of the most generator compatible and environmentally friendly UPS. POWER WALK IN facility helps to achieve gradual connection to oil engine so as to prevent unreliable start of the engine in the parallel operation system, applicable in several voltage systems.

LBS SYNCHRONIZATION (OPTIONAL)

LBS synchronization allows the system synchronization of two sets of UPS. It is suitable for STS (Static Transfer Switch) Dual Bus configuration, in which the STS input, connected to the output of the two independent UPS and the output to the load.

 PERFECT MONITORING

Support RS232 and RS485, LCD screen display, monitoring parts helps monitor the working condition of UPS, give instructions, record fault time and other local monitoring functions, and also help to achieve the communication between UPS lower machine and monitoring upper computer, and control the auxiliary system.

COLD START

The PPXs Series UPS have the option to start the UPS, with battery without mains.

N+X PARALLEL OPERATION MODE (OPTIONAL)

It is convenient to achieve parallel operation. You only need to connect the parallel cables and set the UPS, and the host is automatically produced. In case the host breaks down, the slave automatically becomes the host, which increases the reliability of the system. The system can have at most 6 sets of UPS connected in parallel.

PERFECT PROTECTION

  • Fault Protection for Auxiliary Power Supply
  • Output Overload Protection
  • Output Short- circuit Protection
  • Emergency Power- Off
  • Over-voltage Protection
  • Over-frequency Protection
  • Over-current Protection
  • Over-voltage Protection for Bus Bar
  • Over-temperature Protection
Technical Specification

TECHNICAL SPECIFICATIONS

MODEL PPXs 10 PPXs 15 PPXs 20 PPXs 30 PPXs 40 PPXs 60 PPXs 80 PPXs 100 PPXs 120
CAPACITY 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA
INPUT
Input Wiring Three – Phase five wire (3Φ + N + PE)
Rated Voltage 380 / 400 / 415 VAC
Voltage Range 300V ~ 480V
Rated Frequency 50 / 60 Hz
Frequency Range (50 / 60) ± 5 Hz
Delayed start of rectifier 10s (1 ~ 300 settable)
Bypass voltage range ± 20% (settable)
OUTPUT
Output Wiring Three – Phase five wire (3Φ + N + PE)
Rated Voltage 380 / 400 / 415 VAC
Output Voltage Regulation ± 1%
Output Frequency Regulation 50 / 60 Hz ± 0.1% in battery mode
Waveform Sinusoidal
Voltage Distortion (THDv) ≤ 1% (linear load), ≤ 5% (non-linear load)
Crest Factor 3:1
Overload 110% for 60 min / 125% for 10 min / 150% for 60 sec
BATTERIES
DC Voltage Lead acid battery: 360 or 384 VDC
Number of Batteries 12V 30 Pcs (support 28~32) / 2V 180 Pcs (support 168~300 Pcs)
Charging Current Settable As per Battery Type
*Check with factory for Lithium Ion batteries
SYSTEM
Efficiency Above 90%; Eco Mode ≥ 98%
Max. number of parallel connections 6
Protections Short-circuit, overload, overvoltage, undervoltage, low battery, overtemperature, fan failure
Communications RS232/RS485 / dry contacts (standard), SNMP (optional)
EMI EN62040-2
EMS IEC61000-4-2(ESD), IEC61000-4-3(RS), IEC61000-4-4(EFT), IEC61000-4-5(Surge)
OTHERS
Operating temperature 0 – 50°C
Storage temperature -25°C – 55°C (without batteries)
Relative humidity 0 – 95% (non-condensing)
Altitude ≤ 1000 m (derating 1% for each additional 100 m)
IP rating IP21
Noise level at 1m 65 dB
Dimensions (WxDxH) 400 x 800 x 1100 700 x 700 x 800 x 1700
Pack Dimensions (WxDxH) 490 x 920 x 1300 700 x 800 x 900 x 1850
Net Weight (kg) 158 165 175 210 260 460 590 630 690
Gross Weight (kg) 200 207 217 252 302 480 620 660 720

TECHNICAL SPECIFICATIONS

MODEL PPXs 160 PPXs 200 PPXs 250 PPXs 300 PPXs 400 PPXs 500
CAPACITY 160KVA 200KVA 250KVA 300KVA 400KVA 500KVA
INPUT
Input Wiring Three – Phase five wire (3Φ+ N + PE)
Rated Voltage 380 / 400 / 415 VAC
Voltage Range 300V ~480V
Rated Frequency 50 /60 Hz
Frequency Range (50 /60) ± 5 Hz
Delayed start of rectifier 10s (1 ~ 300 settable)
Bypass voltage range ± 20% (settable)
OUTPUT
Output Wiring Three – Phase five wire (3Φ + N + PE)
Rated Voltage 380 / 400 / 415 VAC
Output Voltage Regulation ± 1%
Output Frequency Regulation 50 /60 Hz ± 0.1% in battery mode
Waveform Sinusoidal
Voltage Distortion (THDv) ≤ 1% (linear load), ≤ 5% (non-linear load)
Crest Factor 3:1
Overload 110% for 60 min / 125% for 10 min / 150% for 60 sec
BATTERIES
DC Voltage 384 V upto 250 kVA 480 V for 300kVA and above
Number of Batteries 12V 30 Pcs upto 250 kVA 12V 40 Pcs for 300kVA and above
Charging Current Charging rate (settable) x battery capacity (settable) x number of battery groups (settable)
SYSTEM
Efficiency Above 90%
Max. number of parallel connections 6
Protections Short-circuit, overload, overvoltage, under voltage, low battery, overtemperature, fan failure
Communications RS232, RS485, dry contacts (standard); SNMP card, temperature compensation, SMS alarms (optional)
Display 5.7 inches LCD touch screen + LED
OTHERS
Operating Temperature 0 – 50°C
Storage Temperature -25°C – 55°C (without batteries)
Relative Humidity 0 – 95% (non-condensing)
Altitude ≤ 1000 m (derating 1% for each additional 100 m)
IP Rating IP21
Noise Level at 1m <65 dB <70 dB
Dimensions (W×D×H) 800×860×1700 1210×860×1950 2380×860×1950
Pack Dimensions (W×D×H) 900×1000×1950 1300×1000×2200 1300×1000×2200 (x2)
Net Weight (kg) 790 1135 1275 1355 2090 2300
Gross Weight (kg) 800 1200 1340 1420 2200 2410